BACnet Device Settings

Here, the BACnet settings of the device can be configured.
- BACnet Device Instance: The object instance of the device (BACnet Device Object). The allowed range is 0 - 4194303.
- BACnet Device Name: The object name property of the BACnet object. The allowed length is 1-31. Only uppercase letters, lowercase letters, digits 0-9, space, comma, and period can be used.
- Max APDU: The maximum APDU length of the BACnet object. Options: 50, 128, 206, 480, 1024, 1476.
- Location: The location property of the BACnet object. The allowed length is 1-31. Only uppercase letters, lowercase letters, digits 0-9, space, comma, and period can be used.
- Description: The description property of the BACnet object. The allowed length is 1-31. Only uppercase letters, lowercase letters, digits 0-9, space, comma, and period can be used.
- Reinitialise Device Password: The password for the reinitialise device service of the DC620 DUAL BACnet IoT Gateway. Maximum length is 20. Only uppercase letters, lowercase letters, digits 0-9, space, comma, and period can be used.