Skip to main content

Modbus Settings

On this page, the user can configure the Modbus settings.

ModbusSettings-ISM842

ParameterDescriptionValues
Modbus ModeThe Modbus mode of the device.Master: The device will operate as a Modbus RTU and Modbus TCP Master.
Slave: The device will operate as a Modbus RTU and Modbus TCP Slave.
Modbus RTU Slave IDThe Slave ID of the device.
Modbus RTU Baud RateThe baud rate of the RTU connection.300, 600, 1200, 2400, 4800, 9600, 19200, 83400, 57600, 115200
Modbus RTU DatabitsThe number of data bits in RTU.5, 6, 7, 8
Modbus RTU ParityThe parity bit of the RTU.Odd, Even, None
Modbus RTU Stop BitsThe stop bit of the RTU transmission.1, 1.5, 2
Modbus TCP ServerEnable or disable the Modbus TCP to RTU gateway.
Modbus TCP Server PortThe port number of the Modbus TCP to RTU gateway.
Modbus TCP Server Timeout

The timeout value for the Modbus RTU response in the Modbus TCP to RTU gateway.

Modbus TCP Server Keep AliveEnable or disable the keep alive feature in the Modbus TCP to RTU gateway.
Modbus TCP Server Keep Alive Idle TimeThe waiting time for the keep alive message from the client in the Modbus TCP - RTU gateway. If the values of Modbus TCP Server Keep Alive Interval and Modbus TCP Server Keep Alive Count are equal to zero, the gateway waits for the Modbus TCP Server Keep Alive Idle Time duration, and if no keep alive message or data is received from the client, the gateway closes the connection. If the values of Modbus TCP Server Keep Alive Interval and Modbus TCP Server Keep Alive Count are different from zero, the gateway waits for the Modbus TCP Server Keep Alive Idle Time duration, and if no keep alive message or data is received from the client, the gateway waits for the Modbus TCP Server Keep Alive Count number of Modbus TCP Server Keep Alive Interval durations and then closes the connection.