Physical Interface
LED
| LEDs | |
|---|---|
| Power LED | Blue: Power on. Off: No power. |
| NET LED | The LED remains on when the device receives an IP address via Wi-Fi or Ethernet. The LED turns off when the device does not receive an IP address. The LED blinks when the device performs IP-based communication. |
| ETH LED | The LED remains on when Ethernet is enabled and the cable is connected. The LED turns off when Ethernet is disabled or the cable is disconnected. |
| RS485 LED | Flashes when data is received or sent through the RS485 ports. |
| RSSI LED | Blue: In Wi-Fi Access Point mode Green: In Station mode, good signal quality Yellow: In Station mode, medium signal quality Red: In Station mode, weak signal quality White: The device could not connect to an Access Point and opened its own Access Point Off: Wi-Fi disabled |
| Digital Input LED | Blue: High level input. Off: Low level input. |
| Digital Output LED | Blue: Relay active. Off: Relay passive. |
Inputs/Outputs
| Digital Inputs | |
|---|---|
| Isolation | Isolated digital inputs, 3.5 kV RMS isolation protection. |
| Input Voltage | 10 - 24 VDC input. |
| Input Group A | In1, In2, In3 digital inputs. C1 COM. |
| Input Group B | In4, In5, In6 digital inputs. C2 COM. |
| Digital Outputs | |
|---|---|
| Output Type | Relay - SPDT - NO/NC (1 Form C) |
| Maximum Contact Voltage | DC: 1 A, 24 VDC AC: 0.5 A, 125 VAC |
| Outputs | NO1: NO normally open, CM1 COM. NC1: NC normally closed, CM1 COM. NO2: NO normally open, CM2 COM. NC2: NC normally closed, CM2 COM. |
| Reset Button | |
|---|---|
| Hold for 1 Second (1 LED active) | The device will restart. |
| Hold for 5 Seconds (2 LEDs active) | The device settings will revert to default values. |
| Hold for 10 Seconds (3 LEDs active) | The device will revert to factory firmware. |
| Antennas | |
|---|---|
| Wi-Fi Antenna | 1x SMA female 50 Ohm |
| RS485 Interface | |
|---|---|
| RS485 Terminal Block | RS485 A+1, B-1, E, A+2, B-2, E terminal block 6x3.5 mm |
| Connection Type | RS485 2 Wire |
| Protection | 15 kV ESD Protection, GDT Protection, Isolated |
| Baud Rate | 300, 600, 1200, 2400, 4800, 9600, 19200, 83400, 57600, 115200 |
| Parity Bits | Odd, Even, None |
| Stop Bit | 1, 1.5, 2 |