REGISTERFUNCTION CODEDESCRIPTIONEXPLANATION
101DIGITAL OUTPUT 1 PULSERead/Write Digital Output 1 Pulse
05
15
201DIGITAL OUTPUT 2 PULSERead/Write Digital Output 2 Pulse
05
15
301DIGITAL OUTPUT 3 PULSERead/Write Digital Output 3 Pulse
05
15
401DIGITAL OUTPUT 4 PULSERead/Write Digital Output 4 Pulse
05
15
501DIGITAL OUTPUT 1 LOCKRead/Write Digital Output 1 Lock
05
15
601DIGITAL OUTPUT 2 LOCKRead/Write Digital Output 2 Lock
05
15
701DIGITAL OUTPUT 3 LOCKRead/Write Digital Output 3 Lock
05
15
801DIGITAL OUTPUT 4 LOCKRead/Write Digital Output 4 Lock
05
15
1000102DIGITAL INPUT 1Status register for digital input 1
1000202DIGITAL INPUT 2Status register for digital input 2
1000302DIGITAL INPUT 3Status register for digital input 3
1000402DIGITAL INPUT 4Status register for digital input 4
1000502DIGITAL INPUT 5Status register for digital input 5
1000602DIGITAL INPUT 6Status register for digital input 6
1000702DIGITAL INPUT 7Status register for digital input 7
1000802DIGITAL INPUT 8Status register for digital input 8
4000103ANALOG INPUT 1 CURRENTGives the current value of the 1st channel of the analog input (mA = X / 1000)
4000203ANALOG INPUT 1 VOLTAGEGives the voltage value of the 1st channel of the analog input (V = X / 1000)
4000303ANALOG INPUT 2 CURRENTGives the current value of the 2nd channel of the analog input (mA = X / 1000)
4000403ANALOG INPUT 2 VOLTAGEGives the voltage value of the 2nd channel of the analog input (V = X / 1000)
4000503DIGITAL INPUTSDigital inputs status query Bit0:Input1 … Bit7:Input8 (0:Inactive, 1:Active)
4000603RSSIRSSI value of the last received RF packet (dBm)
4000703DIGITAL OUTPUTSRead/Write digital outputs pulse Bit0:Output1 … Bit3:Output4 (0:Inactive, 1:Active)
06
16
4000803DIGITAL OUTPUT LOCKSRead/Write digital outputs lock Bit0:Output1 … Bit3:Output4 (0:Inactive, 1:Active)
06
16
4000903DIGITAL OUTPUT 1 PULSE DURATIONDuration for digital output 1 to stay on, Value x 100ms
06
16
4001003DIGITAL OUTPUT 2 PULSE DURATIONDuration for digital output 2 to stay on, Value x 100ms
06
16
4001103DIGITAL OUTPUT 3 PULSE DURATIONDuration for digital output 3 to stay on, Value x 100ms
06
16
4001203DIGITAL OUTPUT 4 PULSE DURATIONDuration for digital output 4 to stay on, Value x 100ms
06
16
40013 - 4002203RETAIN REGISTERSValues are saved to device memory
06
16
40023 - 4010003Reserved for UserReserved for User
06